DocumentCode :
1277968
Title :
Faulty Feeder Detection and Fault Self-Extinguishing by Adaptive Petersen Coil Control
Author :
Lin, Xiangning ; Huang, Jingguang ; Ke, Shuohao
Author_Institution :
Electr. Power Security & High Efficiency Lab., Huazhong Univ. of Sci. & Technol. (HUST), Wuhan, China
Volume :
26
Issue :
2
fYear :
2011
fDate :
4/1/2011 12:00:00 AM
Firstpage :
1290
Lastpage :
1291
Abstract :
The characteristic of the single-phase earth fault in the Peterse coil grounded distribution network is discussed in this paper. It is disclosed that only the derivative of the zero-sequence current of the faulty feeder changes with the controllable inductance of the Petersen coil, while the derivative of the zero-sequence current of the sound feeder is kept invariable. Therefore, a novel faulty feeder selection criterion is proposed. A variety of simulation tests is carried out. The exactness and sensitivity of the proposed scheme are verified by simulation test results.
Keywords :
coils; earthing; fault location; power distribution faults; power distribution protection; adaptive Petersen coil control; coil grounded distribution network; fault self-extinguishing; faulty feeder detection; sound feeder; zero-sequence current; Adaptive Petersen coil; maximum current derivative; residual current; resonant grounding; self-extinguish;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2010.2052964
Filename :
5530342
Link To Document :
بازگشت