Abstract :
This paper presents an accurate fault-location algorithm for double-circuit series-compensated lines. Use of two-end current and voltage signals is taken into account and a more general case of unsynchronized measurements is studied. Different options for analytical synchronization of the measurements are considered. The algorithm applies two subroutines, designated for locating faults on particular line sections, and in addition, the procedure for selecting the valid subroutine. The subroutines are formulated with the use of the generalized fault-loop model, leading to compact formulas. Consideration of the distributed parameter line model ensures high accuracy of the fault location. The proposed selection procedure allows for reliable selection of the valid subroutine. The developed fault-location algorithm has been thoroughly tested using signals taken from Alternate Transients Program-Electromagnetic Transients Program versatile simulations of faults on a double-circuit series-compensated transmission line. The presented fault-location evaluation shows the validity of the derived fault-location algorithm and its high accuracy.
Keywords :
distributed parameter networks; fault location; power engineering computing; power system measurement; power system simulation; power system transients; power transmission faults; transient analysis; transmission network calculations; alternate transients program electromagnetic transients program; analytical synchronization; distributed parameter line model; double circuit series compensated lines; double circuit series compensated transmission line; fault location algorithm; generalized fault loop model; line section; unsynchronized measurements; Circuit faults; Current measurement; EMTP; Fault location; Power system simulation; Alternate Transients Program–Electromagnetic Transients Program (ATP–EMTP); double-circuit line; fault location; series capacitor compensation; simulation; two-end unsynchronized measurements;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2011.2158670
Filename :
5959237
Link To Document :
بازگشت