DocumentCode :
1280863
Title :
Overvoltages in secondary circuits of medium-voltage switchgear generated by multiple reignitions of circuit breakers
Author :
Hardt, Nils ; Koenig, Dieter
Author_Institution :
High-Voltage Lab., Darmstadt Univ. of Technol., Germany
Volume :
41
Issue :
4
fYear :
1999
fDate :
11/1/1999 12:00:00 AM
Firstpage :
510
Lastpage :
515
Abstract :
During switching operations in the high-voltage system, transient voltages and currents occur that can generate overvoltages in the secondary circuits of switchgear. The investigations reported in this article are focused on medium-voltage air-insulated switchgear. The introduced model is able to identify the coupling mechanisms. The coupling via the instrument transformers and the secondary wiring to the electronic equipment is described. At first, the frequency-dependent coupling is explained for each secondary component. These are instrument transformers, the secondary wiring, and the electronic equipment. Then it is shown how to combine these components in order to get a complete description of the interfering mechanisms
Keywords :
air insulation; circuit breakers; electromagnetic compatibility; overvoltage; power system transients; substations; switchgear testing; air-insulated switchgear; coupling mechanisms; electronic equipment; frequency-dependent coupling; instrument transformers; interfering mechanisms; medium-voltage switchgear; multiple circuit breaker reignitions; secondary circuit overvoltages; secondary wiring; substation EMC; switching operations; transient currents; transient voltages; Circuit breakers; Coupling circuits; Electronic equipment; Instrument transformers; Interference; Medium voltage; Substations; Surges; Switchgear; Wiring;
fLanguage :
English
Journal_Title :
Electromagnetic Compatibility, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9375
Type :
jour
DOI :
10.1109/15.809855
Filename :
809855
Link To Document :