• DocumentCode
    1280863
  • Title

    Overvoltages in secondary circuits of medium-voltage switchgear generated by multiple reignitions of circuit breakers

  • Author

    Hardt, Nils ; Koenig, Dieter

  • Author_Institution
    High-Voltage Lab., Darmstadt Univ. of Technol., Germany
  • Volume
    41
  • Issue
    4
  • fYear
    1999
  • fDate
    11/1/1999 12:00:00 AM
  • Firstpage
    510
  • Lastpage
    515
  • Abstract
    During switching operations in the high-voltage system, transient voltages and currents occur that can generate overvoltages in the secondary circuits of switchgear. The investigations reported in this article are focused on medium-voltage air-insulated switchgear. The introduced model is able to identify the coupling mechanisms. The coupling via the instrument transformers and the secondary wiring to the electronic equipment is described. At first, the frequency-dependent coupling is explained for each secondary component. These are instrument transformers, the secondary wiring, and the electronic equipment. Then it is shown how to combine these components in order to get a complete description of the interfering mechanisms
  • Keywords
    air insulation; circuit breakers; electromagnetic compatibility; overvoltage; power system transients; substations; switchgear testing; air-insulated switchgear; coupling mechanisms; electronic equipment; frequency-dependent coupling; instrument transformers; interfering mechanisms; medium-voltage switchgear; multiple circuit breaker reignitions; secondary circuit overvoltages; secondary wiring; substation EMC; switching operations; transient currents; transient voltages; Circuit breakers; Coupling circuits; Electronic equipment; Instrument transformers; Interference; Medium voltage; Substations; Surges; Switchgear; Wiring;
  • fLanguage
    English
  • Journal_Title
    Electromagnetic Compatibility, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9375
  • Type

    jour

  • DOI
    10.1109/15.809855
  • Filename