DocumentCode
1281440
Title
The use of the dynamometer wattmeter for measuring the dielectric power loss and power factor of the insulation of high-tension lead-covered cables
Author
Lee, Everett S.
Author_Institution
General Engineering Laboratory, General Electric Co., Schenectady, N. Y.
Volume
45
Issue
8
fYear
1926
Firstpage
746
Lastpage
754
Abstract
The use of the dynamometer wattmeter for measuring the dielectric power loss and power factor of cable and capacitor insulation is not new, but dates from about 1890. Dynamometer wattmeters as available today are suitable for making these measurements. Care and attention must be given to their application. The usual methods of application are: 1. Compensated dynamometer wattmeter method, with air capacitor, 2. Inductance variation method (phase-defect compensation method), with air capacitor, 3. Series resistor and wattmeter method, 4. Resonance wattmeter method. Comparative measurements of dielectric power loss and power factor of cable samples indicate that results are being obtained with the dynamometer wattmeter wherein the probable departure from the true value is within from 10 to 20 per cent. There is need for an effective means of standardizing any measuring equipment. Study of the calorimeter method for this purpose seems desirable.
fLanguage
English
Journal_Title
A.I.E.E., Journal of the
Publisher
ieee
ISSN
0095-9804
Type
jour
DOI
10.1109/JAIEE.1926.6538408
Filename
6538408
Link To Document