Mitigation of harmonic disturbance at pumped storage power station with static frequency converter
Author
Chiang, Jung-Chen ; Wu, Chi-Jui ; Yen, Shih-Shong
Author_Institution
Dept. of Electr. Eng., Nat. Taiwan Inst. of Technol., Taipei, Taiwan
Volume
12
Issue
3
fYear
1997
fDate
9/1/1997 12:00:00 AM
Firstpage
232
Lastpage
240
Abstract
This paper investigates the harmonic distortion problem and mitigation method at the Mingtan pumped storage power station in Taiwan, where six 300 MVA synchronous generator/motors are started by a static frequency converter (SFC) before the pumping stage. Since the SFC uses a 6-pulse rectifier technique, a large amount of harmonic currents are produced during the starting period. The harmonic distortion level at each bus of the power plant was very high. Especially, the total harmonic distortion (THD) of current at the lighting feeder reached up to 184%, so that power fuses were burned out. At first a 5 mH reactor was inserted in the SFC feeder and a 5th order and high pass filter was installed. However, the harmonic distortion levels were still too high, but there is no space for additional higher-order filters. Finally, the SFC is feeded with an individual transformer and the harmonic disturbance problem is avoided. This paper also gives computer simulations to investigate the harmonic distortion problems and verify the mitigation methods
Keywords
frequency convertors; harmonic distortion; high-pass filters; power filters; power system harmonics; power transformers; pumped-storage power stations; synchronous generators; synchronous motors; 18000 MVA; 300 MVA; computer simulation; field measurements; harmonic currents production; harmonic distortion level; harmonic disturbance mitigation; harmonic disturbance problem; high-pass filter; pumped storage power station; six-pulse rectifier technique; static frequency convertor; synchronous generator/motors; total harmonic distortion; transformer; Frequency conversion; Harmonic distortion; Power generation; Power harmonic filters; Power system harmonics; Rectifiers; Static power converters; Synchronous generators; Synchronous motors; Total harmonic distortion;
fLanguage
English
Journal_Title
Energy Conversion, IEEE Transactions on
Publisher
ieee
ISSN
0885-8969
Type
jour
DOI
10.1109/60.629708
Filename
629708
Link To Document