• DocumentCode
    1282575
  • Title

    Solid-state on-load transformer tap changer

  • Author

    Yousef-Zai, F.Q. ; O´Kelly, D.

  • Author_Institution
    Dept. of Electr. Eng, Univ. of Eng. & Technol., Peshawa, Pakistan
  • Volume
    143
  • Issue
    6
  • fYear
    1996
  • fDate
    11/1/1996 12:00:00 AM
  • Firstpage
    481
  • Lastpage
    491
  • Abstract
    Switching logic is defined for a single-phase transformer tap changer using thyristor switching. A laboratory model validates the theory and shows that tap changing is possible in less than one cycle over the whole power-factor spectrum. Waveform sampling and the use of a microprocessor based control system provides improved control and additional features such as data logging etc. Two schemes are considered for the application of thyristor tap changing to three-phase transformers. Economic viability is strongly dependent on the associated power system and its abnormal operating features, namely system fault currents and especially the degree of exposure of the transformer to lightning surges
  • Keywords
    computerised control; fault currents; microcomputer applications; power engineering computing; power factor; power transformers; surges; switching circuits; thyristor applications; abnormal operating features; data logging; economic viability; lightning surges; microprocessor based control system; power-factor spectrum; single-phase transformer tap changer; solid-state on-load transformer tap changer; switching logic; system fault currents; three-phase transformers; thyristor switching; thyristor tap changing; waveform sampling;
  • fLanguage
    English
  • Journal_Title
    Electric Power Applications, IEE Proceedings -
  • Publisher
    iet
  • ISSN
    1350-2352
  • Type

    jour

  • DOI
    10.1049/ip-epa:19960578
  • Filename
    553466