  • Abstract
    The aim of this study is to investigate the relationship between lowering of the insulation performance of ethylene propylene rubber (EPR) used as a covering material of a cross-linked polyethylene (XLPE) cable and partial discharges (PDs) and to establish a diagnostic technique using an acoustic emission (AE) sensor. An accelerated deterioration test was carried out and then the detected AE signals were evaluated. The results showed that not only the intensity of the AE signal but also the number of counted AE signals of more than a critical value was very useful for diagnosing the EPR. We also proposed a diagnostic sequence using an AE technique.
  • Keywords
    Acoustic emission, Fault diagnosis, Insulator testing, Power cable testing; Acoustic emission; Acoustic materials; Acoustic sensors; Acoustic testing; Attenuation; Cable insulation; Electrodes; Insulation; Joints; Life estimation; Materials; Paramagnetic resonance; Partial discharges; Polyethylene; Power cables; Rubber;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2010.5539696
  • Filename
    5539696