• DocumentCode
    1287484
  • Title

    Design of a novel phasor measurement unit-based transmission line auto reclosing scheme

  • Author

    Khorashadi-Zadeh, H. ; Li, Zuyi

  • Author_Institution
    Transm. & Distrib. Div., Siemens Energy Inc., Wendell, NC, USA
  • Volume
    5
  • Issue
    8
  • fYear
    2011
  • fDate
    8/1/2011 12:00:00 AM
  • Firstpage
    806
  • Lastpage
    813
  • Abstract
    This study presents an adaptive transmission line auto-reclosing scheme based on synchronised phasor measurement units. This scheme uses voltage and current phasors of different sequences at both ends of a transmission line to effectively classify transient and permanent faults occurring on transmission lines. In the case of a transient fault this scheme can provide a variable and adaptive dead time for reclosing circuit breakers via the detection of secondary arc extinction. System simulation studies show that the proposed scheme achieves excellent performance in classifying transient and permanent single-phase faults and estimating the secondary arc extinction time for correct auto-reclosing.
  • Keywords
    circuit-breaking arcs; phase measurement; power transmission faults; power transmission lines; power transmission protection; synchronisation; arc extinction; auto reclosing scheme; circuit breakers; current phasors; permanent faults; phasor measurement unit; synchronisation; transient fault; transmission line; voltage phasors;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission & Distribution, IET
  • Publisher
    iet
  • ISSN
    1751-8687
  • Type

    jour

  • DOI
    10.1049/iet-gtd.2010.0744
  • Filename
    5969511