DocumentCode :
1290752
Title :
Lightning investigation on transmission lines — V
Author :
Lewis, W. ; Foust, C.
Author_Institution :
General Electric Company, Schenectady, N. Y.
Volume :
54
Issue :
9
fYear :
1935
Firstpage :
934
Lastpage :
942
Abstract :
Continuing an investigation of lightning effects on power transmission lines, a recent study confirms previously reached conclusions as to the effectiveness of overhead and buried ground wires. Also, direct stroke surge currents of from 2,000 to 100,000 amperes in tower structures were measured with the surge crest ammeter, and total stroke currents up to 220,000 amperes were indicated. Values for the rate of build-up of direct stroke currents and values of potentials in the tower were obtained. Negative polarity clouds were found to be the source of almost all direct strokes.
fLanguage :
English
Journal_Title :
Electrical Engineering
Publisher :
ieee
ISSN :
0095-9197
Type :
jour
DOI :
10.1109/EE.1935.6540166