Phenomena and Mechanism Analysis on Overvoltages Caused by 40.5-kV Vacuum Circuit Breakers Switching Off Shunt Reactors
Author
Du, Ning ; Guan, Yonggang ; Zhang, Jingsheng ; Niu, Jirong ; Yao, Shuhua ; Xu, Guozheng
Author_Institution
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
Volume
26
Issue
4
fYear
2011
Firstpage
2102
Lastpage
2110
Abstract
In view of frequent and severe overvoltage failures of 40.5-kV vacuum circuit breakers (CBs) while switching off the shunt reactors in the 35-kV distribution systems in China, a series of field tests was carried out to determine the mechanism of this kind of disruption. The transient process and phenomena were analyzed and summarized based on the overvoltage waveforms obtained from the field tests. The experimental results indicated that the probability of reignition is greater for a 40.5-kV CB than in a 12 kV one. The interphase overvoltage was especially critical. The causes of severe overvoltages were analyzed, and it was indicated that the difference of CBs, multireignitions by the interphase coupling, and the different application conditions were the main effect factors. In addition, some suggestions were given.
Keywords
overvoltage; power distribution faults; vacuum breakdown; vacuum circuit breakers; distribution systems; field tests; interphase coupling; interphase overvoltage; overvoltage failures; overvoltage waveforms; shunt reactors; transient process; vacuum circuit breakers; voltage 12 kV; voltage 35 kV; voltage 40.5 kV; Circuit breakers; Power system transients; Shunt (electrical); Surges; Transient analysis; Field test; overvoltage; shunt reactor; switching off; vacuum circuit breaker (VCB);
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2011.2160660
Filename
5978237
Link To Document