    Phenomena and Mechanism Analysis on Overvoltages Caused by 40.5-kV Vacuum Circuit Breakers Switching Off Shunt Reactors

  • Author

    Du, Ning ; Guan, Yonggang ; Zhang, Jingsheng ; Niu, Jirong ; Yao, Shuhua ; Xu, Guozheng

  • Author_Institution
    Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
  • Volume
    26
  • Issue
    4
  • fYear
    2011
  • Firstpage
    2102
  • Lastpage
    2110
  • Abstract
    In view of frequent and severe overvoltage failures of 40.5-kV vacuum circuit breakers (CBs) while switching off the shunt reactors in the 35-kV distribution systems in China, a series of field tests was carried out to determine the mechanism of this kind of disruption. The transient process and phenomena were analyzed and summarized based on the overvoltage waveforms obtained from the field tests. The experimental results indicated that the probability of reignition is greater for a 40.5-kV CB than in a 12 kV one. The interphase overvoltage was especially critical. The causes of severe overvoltages were analyzed, and it was indicated that the difference of CBs, multireignitions by the interphase coupling, and the different application conditions were the main effect factors. In addition, some suggestions were given.
  • Keywords
    overvoltage; power distribution faults; vacuum breakdown; vacuum circuit breakers; distribution systems; field tests; interphase coupling; interphase overvoltage; overvoltage failures; overvoltage waveforms; shunt reactors; transient process; vacuum circuit breakers; voltage 12 kV; voltage 35 kV; voltage 40.5 kV; Circuit breakers; Power system transients; Shunt (electrical); Surges; Transient analysis; Field test; overvoltage; shunt reactor; switching off; vacuum circuit breaker (VCB);
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2011.2160660
  • Filename
    5978237