Abstract :
The insulation system of a dry-type transformer under the combined thermal, electrical, mechanical, and environmental stresses undergoes gradual deterioration, which ultimately leads to transformer failure. It is hence important to test specimen insulation of transformer coil so as to explore the aging law and the associated characteristic parameters related to the insulation condition. This paper proposes a method to evaluate reliability of the insulation system of a dry-type transformer based on the three models of degradation, regression and expert judgment. The three models are developed based on the quality parameters (QPs) from the lab tests. The method is illustrated by estimating the reliability of the insulation system of a mining flameproof dry-type transformer. The accelerated aging tests on the Nomex paper (i.e. the turn-to-turn insulation of the transformer) are conducted. The QPs of the Nomex samples of degree of polymerization, partial discharges, and photomicrograph were measured periodically during aging test. The effectiveness of the proposed method was proved through the lab experiments. The results show that the parameters from the aging test can be used to represent the condition of the insulation system.
Keywords :
ageing; life testing; partial discharges; polymerisation; power transformer insulation; power transformer testing; regression analysis; reliability; Nomex paper; accelerated aging tests; dry type transformer; electrical stress; environmental stress; expert judgment; insulation system reliability; mechanical stress; partial discharge; polymerization degree; quality parameter; regression analysis; reliability assessment; thermal stress; transformer coil; transformer deterioration; transformer failure; turn-to-turn insulation; Aging; Equations; Mathematical model; Oil insulation; Power transformer insulation; Reliability; degree of polymerization; dry-type transformer insulation; partial discharge; photomicrograph; reliability assessment;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2013.6678847
Filename :
6678847
Link To Document :
بازگشت