DocumentCode
1296802
Title
Calculation of Lightning-Induced Voltages on Overhead Distribution Lines Including Insulation Breakdown
Author
De Conti, Alberto ; Perez, Ernesto ; Soto, Edison ; Silveira, Fernando H. ; Visacro, Silvério ; Torres, Horacio
Author_Institution
Lightning Res. Center(LRC), Fed. Univ. of Minas Gerais (UFMG), Belo Horizonte, Brazil
Volume
25
Issue
4
fYear
2010
Firstpage
3078
Lastpage
3084
Abstract
This paper investigates the influence of considering actual insulation volt-time curves both in the calculation of lightning-induced voltages and in the estimation of the number of flashovers an overhead wire may experience per year due to nearby lightning strokes. The flashover mechanism is modeled according with the integration method, which is used as a reference for comparisons with the simplified 1.5 CFO flashover criterion traditionally used in the estimation of the lightning performance of overhead distribution lines. Sensitivity analysis show the dependence of flashovers on the shape and front time of the assumed channel-base current. The obtained results suggest that the simplified 1.5 CFO flashover criterion is likely to underestimate the number of flashovers an overhead line may experience per year due to nearby lightning strokes. This result is confirmed by statistical analyses considering a Monte Carlo-based approach. It is also shown that more realistic flashover rate estimates can be obtained in the statistical analysis of lightning-induced voltages provided a reduced threshold level (1.2 CFO in the particular case evaluated in this paper) is considered instead of the 1.5 CFO level traditionally used in this type of study.
Keywords
Monte Carlo methods; flashover; lightning protection; power cable insulation; power distribution lines; power overhead lines; sensitivity analysis; voltage measurement; CFO flashover criterion; Monte Carlo method; channel-base current; insulation breakdown; insulation volt-time curve; integration method; lightning stroke; lightning-induced voltage calculation; line-critical flashover voltage; overhead distribution line; overhead wire; sensitivity analysis; threshold level; Breakdown voltage; Cable insulation; Flashover; Insulation; Lightning; Power distribution lines; Sensitivity analysis; Shape; Statistical analysis; Threshold voltage; Transient analysis; Wire; Flashover; lightning; lightning-induced voltages; power distribution lines; transient analysis;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2010.2059050
Filename
5549973
Link To Document