• DocumentCode
    1297191
  • Title

    Special tests on impulse circuit breakers

  • Author

    Skeats, Wilfred F.

  • Author_Institution
    General Electric Co., Schenectady, N. Y.
  • Volume
    55
  • Issue
    6
  • fYear
    1936
  • fDate
    6/1/1936 12:00:00 AM
  • Firstpage
    710
  • Lastpage
    717
  • Abstract
    A novel circuit arrangement that supplies a large current to a circuit breaker under test and then subjects the open terminals to a high recovery voltage has been used in testing the 2,500,000-kva 287.5-kv impulse oil circuit breakers built for the Boulder Dam-Los Angeles transmission line. A description of this arrangement, which makes available several times the apparent power of the testing apparatus, is given in this paper, together with oscillograms which show details of the arc extinction process not previously known, and the results of a study of voltage distribution.