• DocumentCode
    1299127
  • Title

    Simulation of transformer PD pulse propagation and monitoring for a 500 kV substation

  • Author

    Dong, Xuzhu ; Zhu, Deheng ; Wang, Changchang ; Tan, Kexiong ; Liu, Yilu

  • Author_Institution
    Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
  • Volume
    6
  • Issue
    6
  • fYear
    1999
  • fDate
    12/1/1999 12:00:00 AM
  • Firstpage
    803
  • Lastpage
    813
  • Abstract
    This paper discusses the development of a simulation model to study the propagation of partial discharge (PD) pulses of transformers in a 500 kV substation. The results will be used to design an on-line PD monitoring system for transformers. The impedance matrix of a 500 kV, single-phase transformer is computed based on geometry data and its external coupling network (often referred to as coupling impedance) is calculated with electromagnetic transients program (EMTP). It was found that the frequency characteristic of the coupling network is complex and that the traditional lumped coupling capacitance representation is only feasible at <60 kHz. The entire substation network was included to calculate the PD propagation of the transformer. PD responses are obtained at the tank grounding and 500 kV bushing tap grounding with a simulated PD pulse injected at the 500 kV terminal and 220 kV terminal of the transformer, respectively. Simulation shows that, using the resonant frequency of the substation network as monitoring frequency, one effectively can increase the monitoring sensitivity. The off-line and on-line PD calibration can also be made based on the developed simulation model
  • Keywords
    earthing; insulation testing; partial discharges; power transformer insulation; power transformer testing; substation insulation; 220 kV; 500 kV; bushing tap grounding; electromagnetic transients program; external coupling network; frequency characteristic; geometry data; impedance matrix; lumped coupling capacitance representation; monitoring frequency; monitoring sensitivity; partial discharge; resonant frequency; simulation model; single-phase transformer; substation; tank grounding; transformer PD pulse propagation; Computational modeling; EMTP; Electromagnetic coupling; Frequency; Grounding; Impedance; Monitoring; Partial discharges; Pulse transformers; Substations;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/94.822019
  • Filename
    822019