    The effect of DC offset on current-operated relays

  • Author

    Stringer, Norman T.

  • Author_Institution
    Basler Electr. Co., Houston, TX, USA
  • Volume
    34
  • Issue
    1
  • fYear
    1998
  • Firstpage
    30
  • Lastpage
    34
  • Abstract
    When a fault occurs on a power system, one or more phases will experience DC offset. This DC component, which will decay dependent on the L/R time constant of the system, can produce saturation in the current transformers, as well as the input current transformers of the protective relays sensing the fault. In addition, when the fault current is interrupted, the resulting DC tail can maintain the current above the relay´s pickup setting for a time dependent on the current transformer secondary circuit L/R time constant. This paper discusses this phenomenon and how it can affect the operation of two types of current-operated relays
  • Keywords
    current transformers; electrical faults; power system protection; power system relaying; power transformers; relay protection; transformer windings; DC offset; L/R time constant; current transformer saturation; current-operated relays; fault sensing; power system faults; power system relay protection; protective relays; transformer secondary; Circuit faults; Coils; Current transformers; Fault currents; Power system protection; Power system relaying; Protective relaying; Relays; Switches; Voltage;