• DocumentCode
    1309093
  • Title

    An advanced interruption method for low-voltage medium-capacity air-break contactors

  • Author

    Mori, Teijiro ; Wada, Yuuichi ; Okado, Hiroyuki ; Masuda, Shigeru

  • Author_Institution
    Mitsubishi Electr. Corp., Hyogo, Japan
  • Volume
    26
  • Issue
    5
  • fYear
    1990
  • Firstpage
    818
  • Lastpage
    823
  • Abstract
    An advanced interruption method with a unique arc-extinguishing plate has been developed on the basis of a study concerning arc extinction of various electrodes in air. The arc-extinguishing plate has a U-shaped portion that projects toward a contact gap. This arrangement markedly reduces the arcing time and contact wear. The short arcing time is revealed by an electric field analysis for various electrodes and by fundamental experiments concerning the effect of the electrode shape on arc extinction. The reduced contact wear is disclosed by an analysis concerning the influence of arc-immobility time on contact wear. This method has been applied to low-voltage contactors of 25, 35, 50, and 65 A frames. It increased the rated operational current for AC3 duty at 660 V by about 50% and reduced the contact wear for AC4 duty at 440 V by about 20%
  • Keywords
    circuit-breaking arcs; contactors; electric fields; switchgear; 25 A; 35 A; 440 V; 50 A; 65 A; 660 V; advanced interruption method; arc-extinguishing plate; arc-immobility time; arcing time; contact gap; contact wear; electric field analysis; electrodes; low-voltage medium-capacity air-break contactors; switchgear; Contactors; Costs; Electrodes; Elementary particle vacuum; Industrial control; Magnetooptic recording; Shape; Solid state circuits; Switching circuits; Vacuum arcs;
  • fLanguage
    English
  • Journal_Title
    Industry Applications, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0093-9994
  • Type

    jour

  • DOI
    10.1109/28.60047
  • Filename