DocumentCode
1309093
Title
An advanced interruption method for low-voltage medium-capacity air-break contactors
Author
Mori, Teijiro ; Wada, Yuuichi ; Okado, Hiroyuki ; Masuda, Shigeru
Author_Institution
Mitsubishi Electr. Corp., Hyogo, Japan
Volume
26
Issue
5
fYear
1990
Firstpage
818
Lastpage
823
Abstract
An advanced interruption method with a unique arc-extinguishing plate has been developed on the basis of a study concerning arc extinction of various electrodes in air. The arc-extinguishing plate has a U-shaped portion that projects toward a contact gap. This arrangement markedly reduces the arcing time and contact wear. The short arcing time is revealed by an electric field analysis for various electrodes and by fundamental experiments concerning the effect of the electrode shape on arc extinction. The reduced contact wear is disclosed by an analysis concerning the influence of arc-immobility time on contact wear. This method has been applied to low-voltage contactors of 25, 35, 50, and 65 A frames. It increased the rated operational current for AC3 duty at 660 V by about 50% and reduced the contact wear for AC4 duty at 440 V by about 20%
Keywords
circuit-breaking arcs; contactors; electric fields; switchgear; 25 A; 35 A; 440 V; 50 A; 65 A; 660 V; advanced interruption method; arc-extinguishing plate; arc-immobility time; arcing time; contact gap; contact wear; electric field analysis; electrodes; low-voltage medium-capacity air-break contactors; switchgear; Contactors; Costs; Electrodes; Elementary particle vacuum; Industrial control; Magnetooptic recording; Shape; Solid state circuits; Switching circuits; Vacuum arcs;
fLanguage
English
Journal_Title
Industry Applications, IEEE Transactions on
Publisher
ieee
ISSN
0093-9994
Type
jour
DOI
10.1109/28.60047
Filename
60047
Link To Document