• DocumentCode
    1309891
  • Title

    Lessons Learned From the Blackout Accident at a Nuclear Power Plant in Taiwan

  • Author

    Lee, Chien-Hsing ; Chen, Bin-Kwie ; Chen, Nan-Ming ; Liu, Chih-Wen

  • Author_Institution
    Dept. of Syst. & Naval Mechatron. Eng., Nat. Cheng Kung Univ., Tainan, Taiwan
  • Volume
    25
  • Issue
    4
  • fYear
    2010
  • Firstpage
    2726
  • Lastpage
    2733
  • Abstract
    A power-failure event occurred at the third nuclear power plant (TNPP) in Taiwan in 2001. A chain of events began at 09:36 p.m. on March 16 due to insulation failure associated with flashovers on the 345-kV transmission line. As a result, the 4.16-kV engineered safety features (ESF) buses at the TNPP experienced a loss of power for 2 h and 8 min. This accident was a class 3 emergency (e.g., a class 4 emergency will lead to an overall evacuation of local residents) based on the declared class of emergency in Taiwan. The purpose of this paper is to describe and analyze the chain of events leading to the loss of electrical power. Conclusions on the causes of the outage are drawn and modifications of the system structure are made to improve safety and reliability in a nuclear power plant.
  • Keywords
    flashover; nuclear power stations; power system reliability; power transmission lines; Taiwan; blackout accident; electrical power; engineered safety features buses; flashovers; insulation failure; nuclear power plant; power failure event; power plant reliability; power plant safety; transmission line; voltage 345 kV; voltage 4.16 kV; Flashover; Generators; Nuclear power generation; Power system reliability; Power transformer insulation; Switches; Voltage control; Insulation flashover; nuclear power plant; power failure; power outage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2010.2050340
  • Filename
    5560703