Abstract :
Reviews the methods for network parameter estimation and correction in power system state estimation and proposes a sequential-type method for real-time processing of transformer tap positions. The method exploits the information contained in the measurement residuals to estimate a better tap position; it uses a linearized sensitivity model to relate the measurement residuals to the tap position error. Based on part of the Belgium HV system, several testing results are reported.
Keywords :
electrical engineering computing; parameter estimation; power systems; power transformers; state estimation; Belgium HV system; linearized sensitivity model; network parameter estimation; parameter correction; power system state estimation; real-time processing; transformer tap positions; Equations; Mathematical model; Measurement uncertainty; Parameter estimation; State estimation; Vectors;