Estimating methodology for a large regional application of conservation voltage reduction
Author
De Steese, J.G. ; Merrick, S.B. ; Kennedy, B.W.
Author_Institution
Pacific Northwest Lab., Richland, WA, USA
Volume
5
Issue
3
fYear
1990
fDate
8/1/1990 12:00:00 AM
Firstpage
862
Lastpage
870
Abstract
The authors describe a supply-curve methodology that can determine the conservation value of CVR (conservation voltage reduction) applied to many distribution systems in a region. It is shown that, in the area served by Bonneville Power Administration involving approximately 150 utilities, the systematic implementation of CVR could conserve between 170 and 268 average Megawatts at a cost of 5 cents/kWh. A large portion of this CVR resource would be available at less than 1 cent/kWh (142 to 230 AMW). The intermediate estimate of the regional CVR resource at 1 cent/kWh (179 AMW) exceeds the conservation potential (150 AMW) that is possible at the same cost from implementing major efficiency improvements (reconductoring, transformer replacement, and voltage upgrading) on Pacific Northwest transmission and distribution systems
Keywords
distribution networks; transmission networks; Bonneville Power Administration; CVR; Pacific Northwest; conservation voltage reduction; distribution networks; reconductoring; supply-curve methodology; transformer replacement; transmission networks; voltage upgrading; ANSI standards; Area measurement; Costs; Energy consumption; Laboratories; Position measurement; Power generation economics; Power industry; Power systems; Voltage;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/59.65915
Filename
65915
Link To Document