DocumentCode :
1317254
Title :
Unit voltage duties in long suspension insulators
Author :
Ryan, Harris J. ; Henline, Henry H.
Author_Institution :
Leland Stanford Jr. University
Volume :
39
Issue :
7
fYear :
1920
fDate :
7/1/1920 12:00:00 AM
Firstpage :
631
Lastpage :
636
Abstract :
POTENTIOMETER measurements were made of the maximum and average voltage duties occurring in strings made up of 10-inch cap and pin type units wherein the numbers of the units were varied from 2 to 20. The numbers of units in the string and their corresponding maximum to average voltage duty-ratios thus obtained were used to locate curve II in Fig. 1. The increase in the duty-ratios is small for the shortest string of two units, it accelerates rapidly as the string is lengthened to 7 units and thereafter it remains constant at the rate of 0.09 per unit added from 7 to 20. Such increase is low and accelerating in short strings of from 2 to 7 units while it is high and constant in long strings of 7 or more units.
Keywords :
Conductors; Insulators; Poles and towers; Strain; Suspensions; Voltage measurement; Weapons;