DocumentCode :
1318087
Title :
Grounded neutral transmission line
Author :
Richards, W.E.
Volume :
38
Issue :
8
fYear :
1919
Firstpage :
1005
Lastpage :
1010
Abstract :
The paper describes the conditions on the system in Toledo which was originally delta-connected. Serious trouble was experienced when a short circuit occurred especially with synchronous apparatus connected to the line which invariably failed due to the voltage drop occasioned by the severe short circuits on the delta system. This trouble was overcome by changing the transmission to a Y system with the neutral grounded. The effect of a short circuit with the new connection has been decidedly minimized.
Keywords :
Circuit faults; Cities and towns; Industries; Joints; Lakes; Poles and towers; Rivers;
fLanguage :
English
Journal_Title :
American Institute of Electrical Engineers, Proceedings of the
Publisher :
ieee
ISSN :
0097-2444
Type :
jour
DOI :
10.1109/PAIEE.1919.6591933
Filename :
6591933
Link To Document :
بازگشت