DocumentCode :
1319943
Title :
Short circuit protection of energy efficient motors
Author :
Heath, Dennis W. ; Bradfield, H.L.
Author_Institution :
Gen. Electr. Co., Plainfield, CT, USA
Volume :
3
Issue :
1
fYear :
1997
Firstpage :
41
Lastpage :
44
Abstract :
Many years ago, the National Electrical Code established a maximum setting for this instantaneous trip breaker of seven times motor full load amperes (FLA), the theory being that that value was just above the typical 6X locked rotor current. In a 1986 IEEE IAS paper Scheda noted that the two most commonly encountered problems in applying high-efficiency motors are (1) replacing a standard motor with a high-efficiency motor, and (2) the need to use thermal sensors on larger machines since higher settings for electronic control would violate the NEC. His paper concludes: “It is suggested that work be done in the industry and standards organizations to serve the needs arising from the use of electronic detection of instantaneous currents for motor protection.” This article addresses some of the work done in the industry to serve these needs and, in particular, how the use of an “electronic detection” inverse time circuit breaker can be appropriately applied when an instantaneous trip breaker would nuisance-trip
Keywords :
circuit breakers; electric motors; energy conservation; motor protection; short-circuit currents; National Electrical Code; energy efficient motors; high-efficiency motors; instantaneous currents detection; instantaneous trip breaker; inverse time circuit breaker; short circuit protection; thermal sensors; AC motors; Circuit breakers; Energy efficiency; Magnetic circuits; Magnetic devices; National electric code; Protective relaying; Rotors; Stator windings; Surge protection;
fLanguage :
English
Journal_Title :
Industry Applications Magazine, IEEE
Publisher :
ieee
ISSN :
1077-2618
Type :
jour
DOI :
10.1109/2943.556930
Filename :
556930
Link To Document :
بازگشت