• DocumentCode
    1323315
  • Title

    Network parameter estimation using online data with application to transformer tap position estimation

  • Author

    Van Cutsem, Thierry ; Quintana, V.H.

  • Author_Institution
    Dept. of Electr. Eng., Liege Univ., Belgium
  • Volume
    135
  • Issue
    1
  • fYear
    1988
  • fDate
    1/1/1988 12:00:00 AM
  • Firstpage
    31
  • Lastpage
    40
  • Abstract
    The authors deal with the estimation of parameters involved in the classical steady-state modelling of network elements within the context of power system state estimation. A general method is proposed for the identification and correction of the real-time data, based on the sensitivity relationship between the measurement residuals and the parameter error; this relationship is treated as an estimation problem, yielding a parameter error estimate. Special emphasis is put on the real-time correction of erroneous transformer tap positions, the most frequent parameter errors during the real-time operation of state estimators. Relationships with other methods are also discussed. Simulation results on a real-life system are reported
  • Keywords
    power systems; power transformers; state estimation; classical steady-state modelling; measurement residuals; network parameter estimation; parameter error; power system state estimation; real-time operation; transformer tap position estimation;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings C
  • Publisher
    iet
  • ISSN
    0143-7046
  • Type

    jour

  • Filename
    6334