DocumentCode :
1327048
Title :
PD pattern analysis during induced test of large power transformers
Author :
Gulski, Edward ; Burger, Hendrik P. ; Vaillancourt, George H. ; Brooks, Roger
Author_Institution :
High Voltage Lab., Delft Univ. of Technol., Netherlands
Volume :
7
Issue :
1
fYear :
2000
fDate :
2/1/2000 12:00:00 AM
Firstpage :
95
Lastpage :
101
Abstract :
The partial discharge (PD) measurements on power transformers are studied with a view toward discrimination and classification of different discharge sources. For this purpose digital analysis is applied to power transformers and reactors going through acceptance testing. Furthermore, based on these measurements, PD databases have been developed to support the discharge evaluation during induced voltage tests of transformers. Using this technique, a clear distinction is possible between transformers showing different discharge behavior
Keywords :
insulation testing; partial discharge measurement; power transformer insulation; power transformer testing; PD pattern analysis; acceptance testing; classification; digital analysis; discharge behavior; discharge evaluation; discharge sources; discrimination; induced voltage tests; power transformers; Databases; Electrodes; Fault location; Laboratories; Partial discharge measurement; Partial discharges; Pattern analysis; Power transformers; Testing; Voltage;