Comparison of dissolved gas-in-oil analysis methods using a dissolved gas-in-oil standard
Author
Lelekakis, Nick ; Martin, Daniel ; Wenyu Guo ; Wijaya, Jaury
Author_Institution
Centre for Power Transformer Monitoring, Diagnostics & Life Manage., Monash Univ., Clayton, VIC, Australia
Volume
27
Issue
5
fYear
2011
Firstpage
29
Lastpage
35
Abstract
Dissolved gas analysis (DGA) is routinely used to determine the concentrations of gases dissolved in the insulating oil of transformers. These concentrations are used to investigate and diagnose electrical or thermal faults [1]. Such faults cause the transformer oil, pressboard, and other insulating materials to de compose and generate gases, some of which dissolve in the oil. The results of DGA must be accurate if faults are to be diag nosed reliably. Commercial testing laboratories understandably prefer measurements that can be made easily and quickly. In this paper, DGA results from five independent testing lab oratories are compared and discussed. A dissolved gas-in-oil standard with known dissolved gas concentrations was used as the basis of comparison.
Keywords
chemical analysis; dissolving; fault diagnosis; power transformer insulation; transformer oil; DGA; dissolved gas analysis; dissolved gas-in-oil standard; electrical faults diagnosis; gas concentration measurement; insulating oil; thermal faults diagnosis; transformer oil; Carbon; Carbon dioxide; Contamination; Dissolved gas analysis; Nitrogen; Transformers; Vacuum systems; Shake Test; dissolved gas analysis; headspace; vacuum extraction;
fLanguage
English
Journal_Title
Electrical Insulation Magazine, IEEE
Publisher
ieee
ISSN
0883-7554
Type
jour
DOI
10.1109/MEI.2011.6025366
Filename
6025366
Link To Document