DocumentCode
1329188
Title
Flashover performance of IEEE standard insulators under ice conditions
Author
Farzaneh, M. ; Kiernicki, J.
Author_Institution
Dept. des Sci. Appliquees, Quebec Univ., Chicoutimi, Que., Canada
Volume
12
Issue
4
fYear
1997
fDate
10/1/1997 12:00:00 AM
Firstpage
1602
Lastpage
1613
Abstract
This paper presents two methods for testing insulators under icing conditions. These methods were based on and developed from those described in the standard of IEC 507, which gives instructions for testing insulators under pollution. The effects of various factors, including wind velocity, ice thickness, dry arcing distance of insulators, and conductivity of freezing water, on the flashover performance of a short string of IEEE standard insulators, were then investigated. The experiments were carried out in a cold room. Moreover, the repercussions of ice on actual insulators were evaluated by examining the maximum withstand stress of the insulators employed on Hydro-Quebec networks and, by comparison, the effects of ice with salt contamination
Keywords
IEEE standards; arcs (electric); electric breakdown; flashover; ice; insulator contamination; insulator testing; IEC 507; IEEE standard insulators; dry arcing distance; flashover performance; freezing water conductivity; ice conditions; ice thickness; maximum withstand stress; polluted insulator testing; salt contamination; wind velocity; Conductivity; Flashover; IEC standards; Ice thickness; Insulation; Insulator testing; Standards development; Stress; Water pollution; Wind speed;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.634180
Filename
634180
Link To Document