DocumentCode :
1329544
Title :
Harmonic evaluation of Benmore converter station when operated as a group connected unit
Author :
Dinh, Q.N. ; Arrillaga, J. ; Wood, A.R. ; Chen, S. ; Enright, W. ; Smith, B.C. ; Du, Z.
Author_Institution :
Canterbury Univ., Christchurch, New Zealand
Volume :
12
Issue :
4
fYear :
1997
fDate :
10/1/1997 12:00:00 AM
Firstpage :
1730
Lastpage :
1735
Abstract :
Three-phase harmonic measurements of a group connected generator-HVDC power converter unit were recently carried out at the Benmore end of the New Zealand HVDC link. This paper describes the test measurement procedures, the set up and configuration of the CHART instrumentation and presents the results which include measured waveforms and their harmonic contents in sequence components for a range of DC line currents. Dynamic simulation accurately predicts the harmonic current contents. The generator harmonic impedances are estimated from the measured and simulated terminal voltages and currents. The generator harmonic ratings for direct connections are also investigated
Keywords :
HVDC power convertors; harmonic distortion; power system analysis computing; power system harmonics; power system measurement; CHART instrumentation; DC line currents; HVDC link; HVDC power converter; New Zealand; computer simulation; dynamic simulation; generator harmonic impedances; generator harmonic ratings; group connected unit; harmonic content; harmonic evaluation; sequence components; test measurement procedures; waveform measurements; Current measurement; HVDC transmission; Impedance measurement; Instruments; Power generation; Power measurement; Power system harmonics; Predictive models; Testing; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.634198
Filename :
634198
Link To Document :
بازگشت