Abstract :
Three-phase harmonic measurements of a group connected generator-HVDC power converter unit were recently carried out at the Benmore end of the New Zealand HVDC link. This paper describes the test measurement procedures, the set up and configuration of the CHART instrumentation and presents the results which include measured waveforms and their harmonic contents in sequence components for a range of DC line currents. Dynamic simulation accurately predicts the harmonic current contents. The generator harmonic impedances are estimated from the measured and simulated terminal voltages and currents. The generator harmonic ratings for direct connections are also investigated
Keywords :
HVDC power convertors; harmonic distortion; power system analysis computing; power system harmonics; power system measurement; CHART instrumentation; DC line currents; HVDC link; HVDC power converter; New Zealand; computer simulation; dynamic simulation; generator harmonic impedances; generator harmonic ratings; group connected unit; harmonic content; harmonic evaluation; sequence components; test measurement procedures; waveform measurements; Current measurement; HVDC transmission; Impedance measurement; Instruments; Power generation; Power measurement; Power system harmonics; Predictive models; Testing; Voltage;
Journal_Title :
Power Delivery, IEEE Transactions on