• DocumentCode
    1329830
  • Title

    Excitation balancing of a self-excited induction generator for maximum power output

  • Author

    Bhattacharya, J.L. ; Woodward, J.L.

  • Author_Institution
    Dept. of Electr. & Electron. Eng., Auckland Univ., New Zealand
  • Volume
    135
  • Issue
    2
  • fYear
    1988
  • fDate
    3/1/1988 12:00:00 AM
  • Firstpage
    88
  • Lastpage
    97
  • Abstract
    Using symmetrical component techniques the steady-state behaviour of a self-excited three-phase induction generator under unbalanced loading is examined. Particular reference is made to single-phase loading, a practical application being the use of standard three-phase cage machines in micro-hydro plants. An unbalanced excitation scheme is proposed which improves balance overall and maximises the allowable power output of a particular machine. A method is presented by which de-rating factor and voltage regulation can be predicted for a general unbalanced condition. The results of modeling are in good agreement with experiment. Possible further applications of the method are to the behaviour of induction generators in networks and the operation of three-phase motors from single-phase supplies
  • Keywords
    asynchronous generators; exciters; load (electric); squirrel cage motors; de-rating factor; maximum power output; micro-hydro plants; self-excited induction generator; single-phase loading; standard three-phase cage machines; steady-state behaviour; symmetrical component techniques; three-phase induction generator; unbalanced excitation scheme; unbalanced loading; voltage regulation;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission and Distribution, IEE Proceedings C
  • Publisher
    iet
  • ISSN
    0143-7046
  • Type

    jour

  • Filename
    6343