DocumentCode
1330382
Title
The maximum safe operating temperature of low-voltage paper-insulated cables
Author
Del Mar, Wm.
Author_Institution
Habirshaw Electric Cable Co.
Volume
40
Issue
2
fYear
1921
Firstpage
131
Lastpage
134
Abstract
The Standards of the Institute state that for low-voltage cables the maximum safe operating temperature is 85 deg. cent. Experiments show that continuous operation at 100 deg. cent. for less than a month, seriously impairs the mechanical condition of impregnated paper. A standard of permissible mechanical condition should, therefore, be established, if such high temperatures are to be allowed. Operation at higher temperatures than allowed by the present Standards is, however, in the nature of a gamble and it is questionable whether the Standards should take cognizance of it.
Keywords
Cable insulation; Heating; Mechanical cables; Moisture; Power cables; Standards;
fLanguage
English
Journal_Title
American Institute of Electrical Engineers, Journal of the
Publisher
ieee
ISSN
0360-6449
Type
jour
DOI
10.1109/JoAIEE.1921.6594189
Filename
6594189