Title :
Current Differential Protection of Transmission Line Using the Moving Window Averaging Technique
Author :
Dambhare, Sanjay ; Soman, S.A. ; Chandorkar, M.C.
Author_Institution :
Dept. of Electr. Eng., Indian Inst. of Technol.-Bombay, Mumbai, India
fDate :
4/1/2010 12:00:00 AM
Abstract :
We propose a new approach to current differential protection of transmission lines. In this approach, we transform the instantaneous line current(s) by using a moving window averaging technique. If the time span of moving window is equal to one-cycle time, then the steady-state value of the transformed current is zero for a periodic signal which is composed of fundamental and harmonic frequencies. Signal distortions (e.g., a fault) cause the transformed currents to deviate from the nominal zero value. This permits the development of a sensitive, secure, fast, and yet simple current differential protection scheme. The scheme can be applied in toto to series-compensated transmission lines. Results on a four-machine ten-bus system and comparative evaluation with state-of-the-art methods brings out promise of the proposed method.
Keywords :
moving average processes; power transmission lines; power transmission protection; current differential protection; four-machine ten-bus system; fundamental frequency; harmonic frequency; instantaneous line current; moving window averaging technique; series-compensated transmission lines; signal distortions; steady-state value; Current differential protection; global positioning system (GPS); moving window averaging technique; series-compensated lines; transmission line;
Journal_Title :
Power Delivery, IEEE Transactions on
DOI :
10.1109/TPWRD.2009.2032324