Short-Circuit Withstand Tests of Metglas 2605SA1-Based Amorphous Distribution Transformers
Author
Mouhamad, Malick ; Elleau, C. ; Mazaleyrat, Frederic ; Guillaume, Callet ; Jarry, B.
Author_Institution
Lab. des Materiels Electr., EDF R&D, Moret sur Loing, France
Volume
47
Issue
10
fYear
2011
Firstpage
4489
Lastpage
4492
Abstract
This paper deals with EDF Research and Development work for ERDF needs in terms of energy efficiency, focused on Amorphous Metal Distribution Transformers (AMDT). Many prototypes built on Metglas 2605SA1, rated 250 to 630 kVA from different manufacturers, were tested under short-circuit conditions according to IEC and ERDF standards. Some of the prototypes exceeded the accepted value of 4% of impedance variation after short-circuit test. Rectangular windings offer poor resistance to short-circuit stresses. Small metal particles, detached from amorphous core, were found at the bottom of the tank. In that case, dielectric strength is not gifted. The results show the active part should be strong enough to support high electrodynamic forces produced during short-circuit test.
Keywords
IEC standards; power transformer testing; short-circuit currents; -circuit stresses; ERDF standard; IEC standard; Metglas 2605SA1; amorphous metal distribution transformers; electrodynamic forces; short-circuit withstand tests; Electrodynamics; Force; Power transformer insulation; Prototypes; Transformer cores; Windings; Amorphous transformers; short-circuit withstand;
fLanguage
English
Journal_Title
Magnetics, IEEE Transactions on
Publisher
ieee
ISSN
0018-9464
Type
jour
DOI
10.1109/TMAG.2011.2155632
Filename
6028095
Link To Document