• DocumentCode
    1331638
  • Title

    Short-Circuit Withstand Tests of Metglas 2605SA1-Based Amorphous Distribution Transformers

  • Author

    Mouhamad, Malick ; Elleau, C. ; Mazaleyrat, Frederic ; Guillaume, Callet ; Jarry, B.

  • Author_Institution
    Lab. des Materiels Electr., EDF R&D, Moret sur Loing, France
  • Volume
    47
  • Issue
    10
  • fYear
    2011
  • Firstpage
    4489
  • Lastpage
    4492
  • Abstract
    This paper deals with EDF Research and Development work for ERDF needs in terms of energy efficiency, focused on Amorphous Metal Distribution Transformers (AMDT). Many prototypes built on Metglas 2605SA1, rated 250 to 630 kVA from different manufacturers, were tested under short-circuit conditions according to IEC and ERDF standards. Some of the prototypes exceeded the accepted value of 4% of impedance variation after short-circuit test. Rectangular windings offer poor resistance to short-circuit stresses. Small metal particles, detached from amorphous core, were found at the bottom of the tank. In that case, dielectric strength is not gifted. The results show the active part should be strong enough to support high electrodynamic forces produced during short-circuit test.
  • Keywords
    IEC standards; power transformer testing; short-circuit currents; -circuit stresses; ERDF standard; IEC standard; Metglas 2605SA1; amorphous metal distribution transformers; electrodynamic forces; short-circuit withstand tests; Electrodynamics; Force; Power transformer insulation; Prototypes; Transformer cores; Windings; Amorphous transformers; short-circuit withstand;
  • fLanguage
    English
  • Journal_Title
    Magnetics, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9464
  • Type

    jour

  • DOI
    10.1109/TMAG.2011.2155632
  • Filename