Abstract :
Several configurations of balanced three-phase series RL loads are investigated to consider the feasibility of using thyristor control with integral-cycle triggering. The four-wire star-connected load, with pairs of thyristors in the supply lines and the delta-connection with pairs of thyristors in the load legs, are found to be suitable. Both connections result in similar load voltage and current waveforms. The branch-delta connection is considered to be preferable because the supply lines do not contain DC components of current.
Keywords :
load (electric); thyristor applications; voltage control; balanced three-phase series RL loads; branch-delta connection; three phase circuits with voltage control; thyristor control with integral-cycle triggering; thyristors; Equations; Harmonic analysis; Switches; TV; Thyristors; Voltage control; Wires;