DocumentCode :
1337450
Title :
Phase-locked oscillator control system for thyristor-controlled reactors
Author :
Ainsworth, J.D.
Author_Institution :
GEC Transmission & Distribution Projects Ltd., Stafford, UK
Volume :
135
Issue :
2
fYear :
1988
fDate :
3/1/1988 12:00:00 AM
Firstpage :
146
Lastpage :
156
Abstract :
The thyristor-controlled reactor (TCR) is used for AC voltage control on transmission lines and industrial busbars. It has a relatively simple main circuit and its performance depends very much on its control system. The phase-locked oscillator type of control system is now universally used for HVDC convertors, and is being introduced for the TCR. The form of this control described is of the `zero-delay´ type, without control filters or other lags, and gives freedom from harmonic instability and a good combination of stability at other frequencies, with fast response. Examples of applications are described briefly
Keywords :
busbars; control systems; oscillators; power transmission lines; reactors (electric); stability; thyristor applications; voltage control; AC voltage control; HVDC convertors; industrial busbars; phase locked oscillators; stability; thyristor-controlled reactors; transmission lines; zero delay control;