DocumentCode :
1337811
Title :
Effect of minor harmonics on the performance of resonant harmonic filters in distribution systems
Author :
Czarnecki, L.S.
Author_Institution :
Dept. of Electr. Eng., Louisiana State Univ., Baton Rouge, LA, USA
Volume :
144
Issue :
5
fYear :
1997
fDate :
9/1/1997 12:00:00 AM
Firstpage :
349
Lastpage :
356
Abstract :
In spite of developing new methods for reducing waveform distortion in distribution systems, resonant harmonic filters (RHFs) remain the main devices for harmonic suppression. With an increase in the number of harmonic generating loads, RHFs often work at the voltage distorted by distant loads inside the supply system. Such filters are used, moreover, for harmonic suppression of not only single loads but also distributed nonlinear loads with a dense harmonic spectrum. Because of this, the load current may contain harmonics other than only those to which the filter is tuned. The voltage harmonics, as well as the current harmonics other than those to which the filter is tuned, are referred to as `minor harmonics´ in this paper. These harmonics are often magnified by RHFs, causing a reduction of the filter effectiveness or even an increase in the waveform distortion. Factors that shape properties and performance of RHFs in distribution systems with minor harmonics are discussed
Keywords :
distribution networks; harmonic distortion; load (electric); power filters; power system harmonics; dense harmonic spectrum; distributed nonlinear loads; distribution systems; harmonic generating loads; harmonic suppression; load current harmonics; minor harmonics effects; resonant harmonic filter performance; waveform distortion;
fLanguage :
English
Journal_Title :
Electric Power Applications, IEE Proceedings -
Publisher :
iet
ISSN :
1350-2352
Type :
jour
DOI :
10.1049/ip-epa:19971206