• DocumentCode
    1338615
  • Title

    Discharges from moving particles in GIS [gas-insulated switchgear]

  • Author

    Holmberg, Magnus E. ; Gubanski, Stanislaw M.

  • Author_Institution
    Dept. of Electr. Power Eng., Chalmers Univ. of Technol., Goteborg, Sweden
  • Volume
    13
  • Issue
    1
  • fYear
    1998
  • fDate
    1/1/1998 12:00:00 AM
  • Firstpage
    17
  • Lastpage
    22
  • Abstract
    The study of the motion of moving metallic particles in GIS requires a good knowledge of the carried charge of the particle. In this paper, measurements of the charging process of a moving particle, performed in a realistic single-phase GIS, are presented. By measuring the charge impulses and the voltage phase at consecutive impacts, it is possible to estimate the carried charge and then compare the results with the existing models of the particle charge. Also, besides the discharges from in-flight corona reported by several authors, it is shown that, for higher voltage levels, several discharges between the particle and the enclosure (outer electrode) can occur as the particle impacts with the enclosure
  • Keywords
    corona; discharges (electric); electric breakdown; gas insulated switchgear; insulation testing; switchgear testing; GIS; charge impulses; discharges; enclosure; gas-insulated switchgear; in-flight corona; moving metallic particles; voltage phase; Charge measurement; Current measurement; Gas insulation; Geographic Information Systems; Particle measurements; Performance evaluation; Phase estimation; Phase measurement; Switchgear; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.660839
  • Filename
    660839