DocumentCode :
1338679
Title :
Time domain spectroscopy measurements for the insulation diagnosis of a current transformer
Author :
Kumar, Anuradha ; Mahajan, Satish M.
Author_Institution :
CG Power Solutions Inc., Riverside, RI, USA
Volume :
18
Issue :
5
fYear :
2011
fDate :
10/1/2011 12:00:00 AM
Firstpage :
1803
Lastpage :
1811
Abstract :
There is a growing need for accurate but nonintrusive insulation diagnostic techniques and better maintenance tools to assay the internal condition of transformers. Classical diagnostic methods and periodic maintenance routines have been in practice for several decades. Some of the newer non-destructive diagnostic techniques are based on the measurement of dielectric response functions in time and frequency domain. Polarization and Depolarization Current (PDC) analysis is an on-site, off-line, time-domain diagnostic technique capable of differentiating the aging effects of paper and oil insulation. In this research work, a medium voltage (69 kV, 1200 A/5 A) current transformer (CT) was subjected to thermally accelerated tests. The elapsed insulation life was calculated as per IEEE C57.91-1995. Insulation diagnostic tests including PDC were performed at various aging stages of the CT. Results indicate that PDC tests can be applied to instrument transformers as well. A correlation between time and frequency domain spectroscopic measurements was also established. Measurement of furanic compounds in the oil was consistent with the paper conductivity trends observed in the PDC measurements.
Keywords :
ageing; current transformers; paper; power transformer insulation; preventive maintenance; time-domain analysis; IEEE C57.91-1995; aging effects; current transformer; depolarization current analysis; dielectric response functions; furanic compounds; insulation diagnosis; nonintrusive insulation diagnostic; oil insulation; paper conductivity; paper insulation; periodic maintenance routines; polarization analysis; thermally accelerated tests; time domain spectroscopy measurements; voltage 69 kV; Current measurement; Current transformers; Dielectric measurements; Dielectrics; Oil insulation; Temperature measurement; Time domain spectroscopy; current transformer; depolarizationcurrent; insulation diagnosis; polarization current; thermal aging.;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2011.6032853
Filename :
6032853
Link To Document :
بازگشت