Power frequency magnetic field management using a combination of active and passive shielding technology
Author :
Hiles, Michael L. ; Olsen, Robert G. ; Holte, Kirby C. ; Jensen, David R. ; Griffing, K.L.
Author_Institution :
Field Manage. Services Corp., Los Angeles, CA, USA
Volume :
13
Issue :
1
fYear :
1998
fDate :
1/1/1998 12:00:00 AM
Firstpage :
171
Lastpage :
179
Abstract :
Power frequency magnetic fields are difficult and expensive to shield, particularly when the fields originate from sources with complicated field patterns. A method is discussed and test data presented which suggests that carefully combining active and passive shielding techniques can produce results which are importantly superior to either technique when used alone. The results are generally consistent with an analysis which considers sources as a superposition of elementary source fields with different order terms
Keywords :
magnetic fields; magnetic shielding; active shielding technology; elementary source fields superposition; field patterns; passive shielding technology; power frequency magnetic field management; Bars; Circuits; Conducting materials; Energy management; Frequency; Geometry; Magnetic fields; Magnetic shielding; Switches; Transformers;