• DocumentCode
    1338875
  • Title

    Development of a high-speed switching system for distribution networks

  • Author

    Genji, Takamu ; Shimamoto, Masao ; Kishida, Koichi

  • Author_Institution
    Tech. Res. Center, Kansai Electr. Power Co. Inc., Amagasaki, Japan
  • Volume
    13
  • Issue
    1
  • fYear
    1998
  • fDate
    1/1/1998 12:00:00 AM
  • Firstpage
    186
  • Lastpage
    193
  • Abstract
    This paper describes a high-speed switching system for distribution networks which has been developed with the aim of improving power supply reliability (reducing the number of supply interruptions) of distribution systems. When a fault occurs in conventional distribution systems, the fault section is isolated using a sequential time-out control scheme which requires the reclosing and re-reclosing of the entire system. A major drawback of such systems is that normal sections are also subjected to unnecessary power supply interruptions. In order to resolve this problem, the authors have developed a high-speed switching system which isolates only the fault section without interrupting the power supply to normal sections. This new system can fully restore power to the normal sections and completely isolate the fault section within 500 ms in the case of a ground fault
  • Keywords
    distribution networks; earthing; electrical faults; power system protection; power system reliability; switching; 500 ms; development; distribution networks; fault section isolation; ground fault; high-speed switching system; power supply interruptions; power supply reliability; sequential time-out control scheme; supply interruptions; Automatic control; Circuit breakers; Circuit faults; Control systems; Electrical fault detection; Joining processes; Power supplies; Switches; Switching circuits; Switching systems;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.660877
  • Filename
    660877