• DocumentCode
    1338915
  • Title

    The IPC technology-a new approach for substation updating with passive short-circuit limitation

  • Author

    Brochu, J. ; Beauregard, F. ; Morin, G. ; Lamay, J. ; Pelletier, P. ; Kheir, S.

  • Author_Institution
    CITEQ, Varenne, Que., Canada
  • Volume
    13
  • Issue
    1
  • fYear
    1998
  • fDate
    1/1/1998 12:00:00 AM
  • Firstpage
    233
  • Lastpage
    240
  • Abstract
    The paper presents a new approach to fault current limitation based on the interphase power controller (IPC) technology. From a power system point of view, this IPC has the same function as a transformer: it handles its share of the load current but, during a fault, it does not contribute to the fault current. It thus allows a substation to be updated without increasing the fault level. A four-transformer 315-120 kV substation is used to illustrate the concept
  • Keywords
    current limiters; power control; short-circuit currents; transformer substations; 120 kV; 315 kV; fault current limitation; four-transformer substation; interphase power controller; load current; passive short-circuit limitation; power system; substation updating; Circuit faults; Fault current limiters; Fault currents; Power system faults; Power system reliability; Senior members; Substations; Superconducting materials; Superconducting transmission lines; Urban areas;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.660883
  • Filename
    660883