• DocumentCode
    1338957
  • Title

    Harmonic impedance measurement using three-phase transients

  • Author

    Nagpal, M. ; Xu, W. ; Sawada, J.

  • Author_Institution
    Powertech Labs. Inc., Surrey, Canada
  • Volume
    13
  • Issue
    1
  • fYear
    1998
  • fDate
    1/1/1998 12:00:00 AM
  • Firstpage
    272
  • Lastpage
    277
  • Abstract
    In this paper, a technique is presented for measuring the harmonic impedances of an unbalanced three-phase distribution feeder. The technique uses transients in bus voltages and feeder currents generated by several close-trip operations of the shunt capacitor bank. The work is based on the assumption that the impedance of the feeder does not change over time during which the switching operations are performed. Mathematical development of the technique is verified with the laboratory and the field tests. The technique provided good measurements of the harmonic impedances up to 1.5 kHz for the given capacitor sizes. Statistical indices were developed to assess the accuracy of the estimated impedance values
  • Keywords
    capacitor storage; distribution networks; electric impedance measurement; power system harmonics; power system measurement; power system transients; switching; transient analysis; bus voltage transients; close-trip operations; feeder currents; feeder impedance; harmonic impedance measurement; shunt capacitor bank; statistical indices; switching operations; three-phase transients; unbalanced three-phase distribution feeder; Aggregates; Capacitors; Frequency; Impedance measurement; Laboratories; Power system harmonics; Power system modeling; Power system simulation; Power system transients; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.660889
  • Filename
    660889