1338957
Title
Harmonic impedance measurement using three-phase transients
Author
Nagpal, M. ; Xu, W. ; Sawada, J.
Author_Institution
Powertech Labs. Inc., Surrey, Canada
Volume
13
Issue
1
fYear
1998
fDate
1/1/1998 12:00:00 AM
Firstpage
272
Lastpage
277
Abstract
In this paper, a technique is presented for measuring the harmonic impedances of an unbalanced three-phase distribution feeder. The technique uses transients in bus voltages and feeder currents generated by several close-trip operations of the shunt capacitor bank. The work is based on the assumption that the impedance of the feeder does not change over time during which the switching operations are performed. Mathematical development of the technique is verified with the laboratory and the field tests. The technique provided good measurements of the harmonic impedances up to 1.5 kHz for the given capacitor sizes. Statistical indices were developed to assess the accuracy of the estimated impedance values
Keywords
capacitor storage; distribution networks; electric impedance measurement; power system harmonics; power system measurement; power system transients; switching; transient analysis; bus voltage transients; close-trip operations; feeder currents; feeder impedance; harmonic impedance measurement; shunt capacitor bank; statistical indices; switching operations; three-phase transients; unbalanced three-phase distribution feeder; Aggregates; Capacitors; Frequency; Impedance measurement; Laboratories; Power system harmonics; Power system modeling; Power system simulation; Power system transients; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.660889
Filename
660889
Link To Document