DocumentCode :
1338957
Title :
Harmonic impedance measurement using three-phase transients
Author :
Nagpal, M. ; Xu, W. ; Sawada, J.
Author_Institution :
Powertech Labs. Inc., Surrey, Canada
Volume :
13
Issue :
1
fYear :
1998
fDate :
1/1/1998 12:00:00 AM
Firstpage :
272
Lastpage :
277
Abstract :
In this paper, a technique is presented for measuring the harmonic impedances of an unbalanced three-phase distribution feeder. The technique uses transients in bus voltages and feeder currents generated by several close-trip operations of the shunt capacitor bank. The work is based on the assumption that the impedance of the feeder does not change over time during which the switching operations are performed. Mathematical development of the technique is verified with the laboratory and the field tests. The technique provided good measurements of the harmonic impedances up to 1.5 kHz for the given capacitor sizes. Statistical indices were developed to assess the accuracy of the estimated impedance values
Keywords :
capacitor storage; distribution networks; electric impedance measurement; power system harmonics; power system measurement; power system transients; switching; transient analysis; bus voltage transients; close-trip operations; feeder currents; feeder impedance; harmonic impedance measurement; shunt capacitor bank; statistical indices; switching operations; three-phase transients; unbalanced three-phase distribution feeder; Aggregates; Capacitors; Frequency; Impedance measurement; Laboratories; Power system harmonics; Power system modeling; Power system simulation; Power system transients; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.660889
Filename :
660889
Link To Document :
بازگشت