DocumentCode
1339184
Title
Development of an interrupting chamber for 1000 kV high-speed grounding switches
Author
Mizoguchi, H. ; Hioki, I. ; Yokota, T. ; Yamagata, Y. ; Tanaka, K.
Author_Institution
Toshiba Corp., Kawasaki, Japan
Volume
13
Issue
2
fYear
1998
fDate
4/1/1998 12:00:00 AM
Firstpage
495
Lastpage
502
Abstract
High-speed grounding switches (HSGS) for 1000 kV (UHV) transmission lines are required to interrupt a delayed zero current with a long arcing time. This requirement was met by allowing pressure rise in the opening operation to last efficiently for a long time through optimizing the exhaust volume and the residual volume of a puffer-type interrupting chamber and utilizing the effect of pressure rises due to arcing
Keywords
circuit-breaking arcs; earthing; fault currents; gas blast circuit breakers; interrupters; power system protection; power transmission lines; 100 kV; UHV transmission lines; arcing time; delayed zero current interruption; exhaust volume; high-speed grounding switches; interrupting chamber development; opening operation; pressure rise; puffer-type interrupting chamber; residual volume; Circuit breakers; Circuit faults; Delay; Electromagnetic induction; Electrostatic induction; Grounding; Power transmission; Power transmission lines; Switches; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.660920
Filename
660920
Link To Document