• DocumentCode
    1339342
  • Title

    Experience with the detection of faulty composite insulators on high-voltage power lines by the electric field measurement method

  • Author

    Vaillancourt, G.H. ; Carignan, S. ; Jean, C.

  • Author_Institution
    Hydro-Quebec, Varennes, Que., Canada
  • Volume
    13
  • Issue
    2
  • fYear
    1998
  • fDate
    4/1/1998 12:00:00 AM
  • Firstpage
    661
  • Lastpage
    666
  • Abstract
    Hydro-Quebec´s experience with polymer insulators began in 1977. A sixteen km section of a 735 kV transmission line near Quebec City was then re-insulated with 282 composite insulators of three different makes in equal proportions. The objective was to study them under real service conditions in order to evaluate their performance and to assess the relative merits of each make. This experimentation was later extended to some other lines and/or voltage levels and has continued up to now. During all these years, various methods of testing composite insulators in-service have been experimented with and early in the 1990s, the first device developed at IREQ for the in-situ testing of porcelain insulators by the electric field method was modified and adapted for use on composite suspension insulators. This paper presents a few cases of insulators having a particularly dangerous type of failure mode and found on the lines by the use of the electric field method. Some background information on the detection of defects by this method is also given and some of the experiments done in the laboratory on composite insulators to define the limits of the method are described
  • Keywords
    composite insulators; electric breakdown; electric field measurement; fault diagnosis; insulator testing; power overhead lines; power system measurement; 735 kV; composite insulator fault detection; electric field measurement method; failure mode; high-voltage power lines; in-service testing; insulation performance; suspension insulators; transmission line; Cities and towns; Dielectrics and electrical insulation; Fault detection; Insulator testing; Laboratories; Plastic insulation; Polymers; Porcelain; Transmission lines; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.660958
  • Filename
    660958