DocumentCode :
1340622
Title :
Protection scheme for transmission lines based on alienation coefficients for current signals
Author :
Masoud, M.E. ; Mahfouz, M.M.A.
Author_Institution :
Electr. Power & Machines Dept., Helwan Univ., Helwan, Egypt
Volume :
4
Issue :
11
fYear :
2010
fDate :
11/1/2010 12:00:00 AM
Firstpage :
1236
Lastpage :
1244
Abstract :
In modern digital power system protection systems, statistical coefficients technique is recently used for fault analysis. An alienation technique is developed for faults detection and discrimination. The proposed technique is able to accurately identify the condition of phase(s) involved in all ten types of shunt faults that may occur in extra high-voltage transmission lines under different fault resistances, inception angle and loading levels. The proposed technique does not need any extra equipment as it depends only on the three line-currents measurements which are mostly available at the relay location. This technique is able to perform the fault detection, type and phase selection in about a half-cycle period. Thus, the proposed technique is well suited for implementation in digital protection schemes. The proposed methodology is applied for a part of 500 KV Egyptian network. Alternative transient program and MATLAB programs are used to implement the proposed technique.
Keywords :
fault diagnosis; power transmission lines; power transmission protection; statistical analysis; Egyptian network; MATLAB programs; alienation coefficients; current signals; digital power system protection systems; extra high-voltage transmission lines; fault analysis; fault detection; fault discrimination; fault resistances; line-currents measurements; shunt faults; statistical coefficients technique; transmission lines; voltage 500 kV;
fLanguage :
English
Journal_Title :
Generation, Transmission & Distribution, IET
Publisher :
iet
ISSN :
1751-8687
Type :
jour
DOI :
10.1049/iet-gtd.2009.0648
Filename :
5593264
Link To Document :
بازگشت