• DocumentCode
    1342569
  • Title

    Directional relays provide differential-type protection on large industrial plant power system

  • Author

    Gilbert, M. M. ; Bell, R. N.

  • Author_Institution
    E. I. du Pont de Nemours and Company, Wilmington, Del.
  • Volume
    74
  • Issue
    4
  • fYear
    1955
  • Firstpage
    220
  • Lastpage
    227
  • Abstract
    SEVERAL years ago it became necessary to revise the primary distribution system in a large chemical plant. This plant was approximately 25 years old and had undergone a rapid expansion during this entire period. The type of electric distribution system which had developed is typical of many other large chemical plants which have expanded over comparable periods of time. The original plant electric system consisted of 2,300-volt generation and primary distribution. Load increases associated with later plant expansions resulted in the introduction of 11,000-volt generation and primary distribution and the installation of an 11,000-volt interconnection with the local public utility. Bus tie reactors had been installed to keep the generator bus fault levels down as additional power capacity was added to the system.
  • Keywords
    Companies; Current transformers; Generators; Inductors; Military aircraft; Protective relaying;
  • fLanguage
    English
  • Journal_Title
    American Institute of Electrical Engineers, Part II: Applications and Industry, Transactions of the
  • Publisher
    ieee
  • ISSN
    0097-2185
  • Type

    jour

  • DOI
    10.1109/TAI.1955.6366382
  • Filename
    6366382