DocumentCode :
1342580
Title :
Relay response to motor residual voltage during automatic transfers
Author :
Kelly, A. R.
Author_Institution :
Esso Research and Engineering Company, Linden, N. J.
Volume :
74
Issue :
4
fYear :
1955
Firstpage :
245
Lastpage :
252
Abstract :
Undervoltage relays and starter solenoids respond to motor residual voltage. Test data are presented showing how such response can affect operation of an automatic transfer in a secondary selective system supplying induction motors. Suggestions are given for relay application.
Keywords :
Equations; Induction motors; Mathematical model; Relays; Stators; Synchronous motors; Time frequency analysis;
fLanguage :
English
Journal_Title :
American Institute of Electrical Engineers, Part II: Applications and Industry, Transactions of the
Publisher :
ieee
ISSN :
0097-2185
Type :
jour
DOI :
10.1109/TAI.1955.6366384
Filename :
6366384
Link To Document :
بازگشت