Title :
New distance relay compensation algorithm for double-circuit transmission line protection
Author :
Seyedi, Heresh ; Behroozi, L.
Author_Institution :
Fac. of Electr. & Comput. Eng., Univ. of Tabriz, Tabriz, Iran
Volume :
5
Issue :
10
fYear :
2011
fDate :
10/1/2011 12:00:00 AM
Firstpage :
1011
Lastpage :
1018
Abstract :
A new zero sequence compensation method is proposed to correct the impedance, estimated by distance relay during the single-circuit operation of double-circuit transmission lines. In the new approach, zero sequence current of the adjacent line is not required for compensation. The new scheme is non-pilot and therefore does not require any communication link. Simulation results verify the dependability and security of the new approach. The over-reach problem, caused by mutual coupling, during far-end faults, is completely resolved by the new method.
Keywords :
compensation; power transmission faults; power transmission lines; power transmission protection; relay protection; communication link; distance relay compensation algorithm; double-circuit transmission line protection; far-end faults; mutual coupling; single-circuit operation; zero sequence compensation method; zero sequence current;
fLanguage :
English
Journal_Title :
Generation, Transmission & Distribution, IET
Publisher :
iet
ISSN :
1751-8687
Type :
jour
DOI :
10.1049/iet-gtd.2011.0029