• DocumentCode
    1343322
  • Title

    New distance relay compensation algorithm for double-circuit transmission line protection

  • Author

    Seyedi, Heresh ; Behroozi, L.

  • Author_Institution
    Fac. of Electr. & Comput. Eng., Univ. of Tabriz, Tabriz, Iran
  • Volume
    5
  • Issue
    10
  • fYear
    2011
  • fDate
    10/1/2011 12:00:00 AM
  • Firstpage
    1011
  • Lastpage
    1018
  • Abstract
    A new zero sequence compensation method is proposed to correct the impedance, estimated by distance relay during the single-circuit operation of double-circuit transmission lines. In the new approach, zero sequence current of the adjacent line is not required for compensation. The new scheme is non-pilot and therefore does not require any communication link. Simulation results verify the dependability and security of the new approach. The over-reach problem, caused by mutual coupling, during far-end faults, is completely resolved by the new method.
  • Keywords
    compensation; power transmission faults; power transmission lines; power transmission protection; relay protection; communication link; distance relay compensation algorithm; double-circuit transmission line protection; far-end faults; mutual coupling; single-circuit operation; zero sequence compensation method; zero sequence current;
  • fLanguage
    English
  • Journal_Title
    Generation, Transmission & Distribution, IET
  • Publisher
    iet
  • ISSN
    1751-8687
  • Type

    jour

  • DOI
    10.1049/iet-gtd.2011.0029
  • Filename
    6036109