DocumentCode :
1344183
Title :
Lightning attachment models and maximum shielding failure current of overhead transmission lines: implications in insulation coordination of substations
Author :
Mikropoulos, P. ; Tsovilis, Thomas E.
Author_Institution :
Dept. of Electr. Energy, Aristotle Univ. of Thessaloniki, Thessaloniki, Greece
Volume :
4
Issue :
12
fYear :
2010
fDate :
12/1/2010 12:00:00 AM
Firstpage :
1299
Lastpage :
1313
Abstract :
The maximum shielding failure current of overhead transmission lines is an important parameter in evaluating the shielding performance of the lines and in insulation coordination of substations. General expressions for the estimation of the maximum shielding failure current of transmission lines, derived by employing several lightning attachment models in shielding analysis, are presented. An application to typical 110 kV up to 1150 kV overhead transmission lines shows that there is a great variability in maximum shielding failure current among lightning attachment models. The importance of maximum shielding failure current in insulation coordination of substations is demonstrated with the aid of alternative transients program-electromagnetic transients program (ATP-EMTP) simulations. The computed overvoltages impinging on 150 and 400 kV gas insulated system (GIS) substations because of shielding failure of the incoming overhead transmission lines, being dependent upon shielding failure current, vary with the lightning attachment model employed in shielding analysis of the lines. Implementation of the electrogeometric model adopted by IEEE Std 1243:1997 in shielding analysis imposes high requirements on protection of the substations against incoming shielding failure surges.
Keywords :
EMTP; cable shielding; lightning protection; power overhead lines; substation insulation; ATP-EMTP simulations; IEEE Std 1243:1997; electrogeometric model; insulation coordination; lightning attachment models; maximum shielding failure current; overhead transmission lines; shielding performance; substations; voltage 150 kV to 400 kV;
fLanguage :
English
Journal_Title :
Generation, Transmission & Distribution, IET
Publisher :
iet
ISSN :
1751-8687
Type :
jour
DOI :
10.1049/iet-gtd.2009.0685
Filename :
5595106
Link To Document :
بازگشت