DocumentCode :
1344997
Title :
Lightning impulse voltage and overshoot evaluation proposed in drafts of IEC 60060-1 and future UHV testing
Author :
Hinow, Martin ; Hauschild, Wolfgang ; Gockenbach, Ernst
Author_Institution :
HIGHVOLT Pruftechnik Dresden GmbH, Dresden, Germany
Volume :
17
Issue :
5
fYear :
2010
fDate :
10/1/2010 12:00:00 AM
Firstpage :
1628
Lastpage :
1634
Abstract :
Lightning impulse (LI) voltage testing is an indispensable method for quality assurance of high voltage (HV) and ultra high voltage (UHV) insulation. Not avoidable parasite inductances of the testing circuit provide an oscillation, known as overshoot, at the peak of the lightning impulse (LI). The present paper gives an overview of existing and proposed overshoot evaluation methods of LI voltage. An analytic derivation clarifies the relation between an overshoot magnitude- and overshoot magnitude-/duration- considering method. Hence the finding is derived that both methods provide similar results by applying power transformer testing. Moreover the current paper identifies that a higher permitted overshoot is required for UHV testing by keeping the front time of T1=1.2 μs.
Keywords :
circuit testing; impulse testing; insulation testing; lightning protection; IEC 60060-1; UHV testing; high voltage quality assurance; lightning impulse voltage testing; overshoot evaluation methods; ultra high voltage insulation; Equations; Generators; IEC standards; Lightning; Oscillators; Power transformers; Testing; Lightning impulse, overshoot, ultra high voltage testing, k-factor;
fLanguage :
English
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
Publisher :
ieee
ISSN :
1070-9878
Type :
jour
DOI :
10.1109/TDEI.2010.5595567
Filename :
5595567
Link To Document :