DocumentCode
134661
Title
Fault location in distribution systems based on smart feeder meters
Author
Trindade, Fernanda ; Freitas, Wilson ; de Melo Vieira, Jose Carlos
Author_Institution
Dept. of Electr. Energy Syst., Univ. of Campinas, Campinas, Brazil
fYear
2014
fDate
27-31 July 2014
Firstpage
1
Lastpage
1
Abstract
Summary form only given. This paper proposes a fault-location method based on smart feeder meters with voltage sag monitoring capability. The main idea is to explore voltage measurements from monitors placed in different buses of distribution systems to estimate the fault location. The estimation is achieved by relating the voltage deviation measured by each meter to the fault current calculated based on the bus impedance matrix, considering the fault in different points. In order to improve the method accuracy, the loads are represented by constant impedance models and included into the bus impedance matrix. The performance of the proposed method is demonstrated by using a real distribution system. Sensitivity studies results show that the method is robust since it has good performance for different values of fault resistance, quantity, and location of the smart meters.
Keywords
fault location; matrix algebra; power distribution faults; power supply quality; smart meters; voltage measurement; bus impedance matrix; fault current calculation; fault resistance; fault-location method; real distribution systems; smart feeder meters; voltage deviation measurements; voltage sag monitoring capability; Educational institutions; Estimation; Fault location; Impedance; Monitoring; Voltage fluctuations; Voltage measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
PES General Meeting | Conference & Exposition, 2014 IEEE
Conference_Location
National Harbor, MD
Type
conf
DOI
10.1109/PESGM.2014.6938809