Title :
Distributing large single-phase loads in limited-capacity 3-phase power systems
Author :
Aroyan, F. George ; Lakey, G. Keith
Author_Institution :
University of California, Berkeley, Calif.
Abstract :
A LARGE single-phase load drawn from a limited-capacity 3-phase system will unbalance the 3-phase system. If analyzed by symmetrical components in the 3-phase system, equal and opposite positive- and negative-sequence currents are realized. This unbalance leads to excessive heating in the stator of the alternator, thus substantially reducing its over-all capacity. If uncorrected, the unbalance may also cause local hot spots in ordinary induction motors.
Keywords :
Capacitors; Friction; Hysteresis; Integrated circuits; Relays; Servomotors;
Journal_Title :
American Institute of Electrical Engineers, Part II: Applications and Industry, Transactions of the
DOI :
10.1109/TAI.1956.6367179